A new generation of engineers has realized they can push heat pumps to the limit.

  • @evranch@lemmy.ca
    link
    fedilink
    55 months ago

    Double would be a COP of over 10. That’s a stretch for an overbuilt GSHP and not even slightly feasible for air-air.

    High COPs are usually easy on a compressor as they represent low compression ratios and low differential temps. For example I can hit around COP 7 in cooling on my scrap heap GSHP, with an evap temp around 10C and condenser temp around 20C. That’s a high side pressure around 100 psi and only 30 psi of differential, “barely working” as far as the compressor is concerned.

    The only way I know to get high COPs is to have an oversized condenser and a way to get your refrigerant below ambient, like evaporative, ground source or overnight radiant so you can get the compression ratio down, unless you know a secret in which case I’m not afraid to burn out a compressor or two trying it out!

    • Kairos
      link
      fedilink
      15 months ago

      I don’t rember the details of how it works. I think it just reduces the torque or something? Maybe it doesn’t work on newer pumps or they already do it.

      • @evranch@lemmy.ca
        link
        fedilink
        45 months ago

        Oh I think I know what you’re talking about, abusing a minisplit by idling the inverter back too far. Effectively you have a hugely oversized condenser for the tiny flow, under the right conditions like a cool night you can get ridiculous subcooling.

        But COP is irrelevant in this case because you’ve derated the actual BTU to near zero, you aren’t moving any refrigerant.

        Also yes this will kill your compressor because the minimum speed is set where it will get enough oil flow. Run it too slow, and it won’t pick up oil and eventually seize up. You also could end up running the suction in vacuum which is also hard on compressors.